3745-82-02 Secondary maximum contaminant levels. The secondary maximum contaminant levels for public water systems are as follows: Contaminant Level Aluminum* . . . . . . . . . . . 0.05 to 0.2 mg/L Chloride. . . . . . . . . . . . 250 mg/L Color . . . . . . . . . . . . . 15 color units Corrosivity . . . . . . . . . . non-corrosive Fluoride. . . . . . . . . . . . 2.0 mg/L Foaming Agents. . . . . . . . . 0.5 mg/L Iron. . . . . . . . . . . . . . 0.3 mg/L Manganese . . . . . . . . . . . 0.05 mg/L Odor . . . . . . . . . . . . . 3 threshold odor number pH. . . . . . . . . . . . . . . 7.0-10.5 Silver. . . . . . . . . . . . . 0.1 mg/L Sulfate . . . . . . . . . . . . 250 mg/L Total dissolved solids (TDS). . 500 mg/L Zinc. . . . . . . . . . . . . . 5 mg/L *The secondary maximum contaminant level for aluminum is a range, with the precise level applicable to each public water system to be determined by the director. Effective: September 13, 1993 Promulgated under: RC Chapter 119 Rule amplifies: RC Section 6109.04 Prior effective dates: 11/26/80, 3/1/88